GeoSource® 2000 - Commercial Pumps - Performance Ratings

ISO 13256-1: Ground Loop

Rated according to ISO Standard 13256-1, which includes power consumption for water pumping.
HEATING
32°F EWT
COOLING
77°F EWT
MODEL
CFM
GPM
MBTUH
COP
MBTU/hr
EER
GH980
2,700
22
78.0
3.3
79.4
12.4
GH1200
3,150
26
91.7
3.1
110.0
10.9

ISO 13256-1: Ground Water

HEATING
50°F EWT
COOLING
59°F EWT
MODEL
CFM
GPM
MBTUH COP MBTUH EER
GH980
2,700
16
88.0
3.5
92.0
14.7
GH1200
3,150
18
102.0
3.2
94.4
13.3

 