| Where You'll find comfort in Heating and Cooling | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
Dealer Locator | Case Studies | About ECONAR | Contact Information | Home
GeoSource® 2000 - Commercial Pumps - Performance Ratings
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Rated according to ISO Standard 13256-1, which includes power consumption for water pumping. |
HEATING
32°F EWT |
COOLING
77°F EWT |
||||
|
MODEL
|
CFM
|
GPM
|
MBTUH
|
COP
|
MBTU/hr
|
EER
|
| GH980 |
2,700 |
22 |
78.0 |
3.3 |
79.4 |
12.4 |
| GH1200 |
3,150 |
26 |
91.7 |
3.1 |
110.0 |
10.9 |
|
HEATING
50°F EWT |
COOLING
59°F EWT |
|||||
|
MODEL
|
CFM
|
GPM
|
MBTUH | COP | MBTUH | EER |
| GH980 |
2,700 |
16 |
88.0 |
3.5 |
92.0 |
14.7 |
| GH1200 |
3,150 |
18 |
102.0 |
3.2 |
94.4 |
13.3 |
![]()